IEC designation |
Mechanical failing load |
Nominal Diameter D |
Nominal Spacing P |
Creepage distance L |
Socket coupling |
Wet power frequency withstand voltage |
Dry lightning impulse withstand voltage |
Power frequency puncture voltage |
Net weight |
kn | mm | mm | mm | mm | kv | kv | kv | kg | |
U70BSA | 70 | 380 | 127 | 365 | 16 | 45 | 90 | 130 | 5.2 |
U70BLA | 70 | 380 | 146 | 365 | 16 | 45 | 90 | 130 | 5.3 |
U100BSA | 100 | 380 | 127 | 365 | 16 | 45 | 90 | 130 | 5.2 |
U100BLA | 100 | 380 | 146 | 365 | 16 | 45 | 90 | 130 | 5.3 |
U120BSA | 120 | 380 | 127 | 365 | 16 | 45 | 90 | 130 | 5.2 |
U120BLA | 120 | 380 | 146 | 365 | 16 | 45 | 90 | 130 | 5.3 |
U160BSA | 160 | 420 | 146 | 380 | 20 | 50 | 95 | 130 | 7.2 |
U160BMA | 160 | 420 | 155 | 380 | 20 | 50 | 95 | 130 | 7.3 |
U210AD | 210 | 420 | 170 | 380 | 20 | 50 | 95 | 130 | 7.3 |
U240AD | 240 | 420 | 170 | 380 | 20/24 | 50 | 95 | 130 | 7.5 |
U300AD | 300 | 420 | 195 | 465 | 28 | 50 | 95 | 130 | 12 |
Power frequency electric arc voltage:0.12s/20ka | |||||||||
Impulse puncture voltage:2.8 P.U | |||||||||
Corona visual test :18P/22C kV | |||||||||
Radio interference voltage(10kV 1MHz):50μv |